Question

A 3-phase grid-connected voltage source converter with DC link voltage of 1000 V is switched using sinusoidal Pulse Width Modulation (PWM) technique. If the grid phase current is 10 A and the 3-phase complex power supplied by the converter is given by (– 4000 – j3000) VA, then the modulation index used in sinusoidal PWM is ______. (round off to two decimal places).

Show Answer

Answer :

0.471 (Range : 0.46 to 0.48)

Given :

(i) 3-phase grid connected voltage source converter with DC link

Vdc= 1000V using sinusoidal pulse with modulation (PWM)

(ii) Grid phase current IL=10A

(iii) S = (– 4000 – j3000) VA

The modulation index. The expression of fundamental phase voltage of 3-phase sinusoidal PWM

(vph)01=m Vdc/2 sin(ωt)

√3vL01(rms)