Question

A three-phase cylindrical rotor synchronous generator has a synchronous reactance XS and a negligible armature resistance. The magnitude of per phase terminal voltage is VA and the magnitude of per phase induced emf is EA . Considering the following two statements P and Q.

P : For any three-phase balanced leading load connected across the terminals of this synchronous generator, VA is always more than EA .

Q : For any three-phase balanced lagging load connected across the terminals of this synchronous generator, VA is always less than EA .

Options :

  1. P is true and Q is false

  2. P is true and Q is true.

  3. P is false and Q is false.

  4. P is false and Q is true.

Show Answer

Answer :

P is true and Q is true.