Question
A three-phase cylindrical rotor synchronous generator has a synchronous reactance XS and a negligible armature resistance. The magnitude of per phase terminal voltage is VA and the magnitude of per phase induced emf is EA . Considering the following two statements P and Q.
P : For any three-phase balanced leading load connected across the terminals of this synchronous generator, VA is always more than EA .
Q : For any three-phase balanced lagging load connected across the terminals of this synchronous generator, VA is always less than EA .
Options :
P is true and Q is false
P is true and Q is true.
P is false and Q is false.
P is false and Q is true.
Answer :
P is true and Q is true.