Question

Two generating units rated for 250 MW and 400 MW have governor speed regulations of 6% and 6.4%, respectively, from no load to full load. Both the generating units are operating in parallel to share a load of 500 MW. Assuming free governor action, the load shared in MW, by the 250 MW generating unit is ______. (round off to nearest integer)

Show Answer

Answer :

200 (Range : 188 to 192 or 198 to 202)