Question
Two generators have cost functions F1 and F2 . Their incremental-cost characteristics are
and
They need to deliver a combined load of 260 MW. Ignoring the network losses, for economic operation, the generations P1 and P2 (in MW) are
Options :
P1=P2=130
P1=160 ,P2=100
P1=140,P2=120
P1=120,P2=140
Answer :
P1=160 ,P2=100
Solution :
Total delivering power is
P1 + P2 = 260 MW .....(1)
The incremental cost of Generator-1 is
The incremental cost of Generator-2 is
For the optimum cost, the incremental cost of each generator must be equal.
IC1 = IC2
⇒ 40 + 0.2 P1 = 32 + 0.4 P2
⇒ 0.2 P1 - 0.4 P2 = - 8 .....(2)
By solving equations (1) and (2), we get
P1 = 160 MW
P2 = 100 MW