Question
Windings ‘A’, ‘B’ and ‘C’ have 20 turns each and are wound on the same iron core as shown, along with winding "X' which has 2 turns. The figure shows the sense (clockwise/anti-clockwise) of each of the windings only and does not reflect the exact number of turns. If windings 'A', 'B' and 'C' are supplied with balanced 3-pbase voltages at 50 Hz and there is no core saturation, the no-load RMS voltage (in V, rounded off to 2 decimal places) across winding "X" is ________.
Answer :
Ans. 46